Eaton E Series DX30/40kVA B380/400/415V 50/60Hz(3-phase input/output)User GuidePDF created with pdfFactory Pro trial version www.pdffactory.com
62.4 Exterior view① AC: This light and inverter light will turn "green" when UPS is powered by Rectifier Input;② Inverter: This light will t
7CHGR FAN Front view(door open)Battery traysPDF created with pdfFactory Pro trial version www.pdffactory.com
83 Technical data3.1 Standards Product IEC62040-3:1999 and EN62040-3:2001 UPS
93.5 AC input3.4 Characteristics 30kVA B 40kVA
103.7 AC output3.8 Battery and ChargerInternal battery package Panasonic LC-RW 1245W / CSB HR 1234WF2Dimensions
114 Mechanical installation4.1 Delivery checkThe UPS and accessories are delivered on a specifically designed pallet that is easy to movewith a forkli
12Check the information on the type designation label of the equipment to verify that the unit isof the correct type. The type designation label inclu
13Preparation for installation.1. Avoid extremes of ambient temperature; excessive dust, moisture or vibration; flammablegases; and corrosive or explo
14Caution!UPS cabinet(s) can fall over if the installation brake pads are not used. Both rear andfront pads must be used to secure the UPS cabinet to
15The normal positions of the MBS switches.The switching sequence for circuit breaker from normal position to maintenance position:PDF created with pd
©2010 Eaton CorporationAll Rights ReservedThe contents of this manual are the copyright of the publisher and may not bereproduced (even extracts) unle
16The maintenance positions of the MBS switches2.Use LCD to turn the UPS from normal mode to bypass mode:Switch-off action (press ESC to exit above pi
171)Switch-off picture 2)If it is in single machine mode, the
187.UPS is now in the maintenance bypass mode, see below (Note: the Serv disconnect i.e.battery breaker must be turned off):Transfer UPS from maintena
19Then the UPS turn to bypass mode.4.Turn ON the Rectifier Input switch and battery breaker.5.Use LCD to turn the UPS from bypass mode to normal mode:
206.UPS is now in the normal mode,see below:7.Remount the locking plate of maintenance switch to the position to prevent the use of it.PDF created wit
215 Electrical installation5.1 Electrical PreparationsThe UPS unit has the following power connections:Three-phase (L1, L2, L3), Neutral (N) and Prote
221.If UPS rectifier input and bypass input are supplied from two mains:Connect the mains 1 supply cables to the UPS rectifier input terminals L1, L2,
23Terminal block diagramWarning!High touch current earth connection essential before connecting supply.2.If UPS rectifier input and bypass in
24The conductor cross sections apply for maximum currents:(1) For PVC-insulated copper cables (at 70℃)(2) When routed in conduits for electrical insta
25Routing of communication cables or data lines should be kept separate from the UPS input,output, and external battery cables.Use cable cross section
4.1 Delivery check………………………………………………………………………4.2 Unpacking and visual inspection………………………………………………4.3 Planning before installation……………………………………………………
26Notice!The following label must be displayed on all switching devices installed in the sameelectrical system as the UPS, even when these are located
27Step1: Put batteries into the trays (see Fig. 2).Fig. 23. Assemble the battery packs.There are eight batteries in each battery pack, four packs inea
28Step3: Install the top tray downward, and fold both the top and bottom tray flanges (see Fig5).Fig. 5Please refer to the following figure(Fig.4) for
29Step4: Tape two sides (see Fig.6 ).Make sure the cable is placed between the tray edgesduring tape mounting.Fig. 6 Front
304. Put the battery packs into the enclosure from left to right and bottom to top and cover eachshelf with a fix-plate(see Fig. 9) (please refer to F
315. Connect the cables to each shelf respectively (see Fig. 10).Fig. 10PDF created with pdfFactory Pro trial version www.pdffactory.com
32Fig.116. Secure each fix-plate with four screws (see Fig. 11).Remark: make sure to connect wires with the same color.7. Tie up the wires properly(se
33Remark:The following warnings should be observed during the operation:-The batteries may contain potential electric shock danger because of high vol
34Notice!The most common battery type used in UPS installations is the valve regulated battery.Valve regulated cells are not sealed. The amount of gas
355.6 Connections between battery cabinet and UPSMake sure the Protective Earthing (PE) connected first.External Battery Cabinet ConnectionsNotice!The
Recycling the used UPS or battery………………………………………………Maintenance……………………………………………………………………………Parallel systems…………….…………………………………………………………8.9.10.Electric
36Exchanging batteriesWarning!If a battery cabinet has been disconnected and is to be reconnected, the batteryisolator may only be reconnected after y
376 Software and connectivityThe Series provide Intelligent Slot, Expanded Slot, PARALLEL, AS400, EPO, RS485 andRS232 as well as SERVICE Supervising C
38RS232 portRS485 portPDF created with pdfFactory Pro trial version www.pdffactory.com
39AS400 portNote!The UPS have to be manually reset if remote shutdown occurs.PDF created with pdfFactory Pro trial version www.pdffactory.com
407 User operations7.1 Single machine operationWarning!High touch current earth connection essential before connecting supply.The only user operations
413)Press ESC to access or automaticallywithin 1min with no button being pressed4)Press ▼ to obtain the below informa-tionRemark: the following drawin
425)Press ▼ again to obtain the below 6)Press ▼ again to obtain the belowinformation
431)Switch-on picture 2)Press ENTER4. Start-up action (press ESC to exit the above picture)Note!If mal
443)Select “Yes, Confirm” to switch on 4)Normal Switch-onthe machine5)Battery power supply (switch off line input switch)PDF crea
453)If it is in parallel machine mode, the 4)Press ENTERfollowing will appear5. Switch-off action (press ESC to exit above pictur
11 Safety instructionsWarning!Operations inside the UPS must be performed by a service engineer from the manufac-turer or from an agent authorised by
465)Select “Yes, Confirm” to switch off 6)Normal Switch-offthe machineNote!If you intend to switch off only one set of UPS among t
473)Enter respective password 4)Select action item8. The Series is capable of DC start-up without AC input, panel disp
489. Procedures of DC switch-on: Activate DC switch-on function set under UPS bypass mode Make sure that “+”, “-” and “N” wires of batteries are p
49Parallel machine wire connection drawing(one battery supply)Parallel machine wire connection drawing(separate battery supply)PDF created with pdfFac
50Single machine wire connection drawingPDF created with pdfFactory Pro trial version www.pdffactory.com
51Eaton DX 30/40 kVA B requires minimum maintenance.1. If battery is switched off, loaded equipments will not be covered for power-off protection.2. M
52Remark:A. Prior to battery replacement, switch off UPS and remove it from AC and battery, take offinternal battery breaker.B. Take off metallic arti
538.2 Regular service/intervalsThe UPS requires very little maintenance if installed in an appropriate environment. In order toensure maximum availabi
549 Parallel systemsParallel is only connected to identical ports for the UPS of same models and kVA rating.1) Follow installation instructions for ge
55Note!Parallel signal cable should be connected as a loop.PDF created with pdfFactory Pro trial version www.pdffactory.com
21.3 CE markingThe product has the CE marking in compliance with the following European directives:LVD Directive (Safety) 2006/95
5610 Recycling the used UPS or batteryBefore scrapping UPS or its battery cabinet, the battery bank must be removed. Localrequirements must be followe
5711 WarrantyThe product is warranted against defects in design, materials and workmanship for a periodof twelve (12) months from its original date of
5812 Display reference TablePDF created with pdfFactory Pro trial version www.pdffactory.com
59Should any display or warning message excluded in the above table be found,please con-tact distributor or call EATON Hot line for advice.● Indicator
31.5 EnvironmentThe UPS must be installed according to the recommendations in this manual.Under no circum-stances the UPS should be installed in an ai
42 Introduction2.1 System descriptionEaton E Series DX products are high-efficiency and high-performance, double conversion,pure-online and three phas
52.2 Basic system configuration2.3 Panel figurePDF created with pdfFactory Pro trial version www.pdffactory.com
Commentaires sur ces manuels