2. Installation
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and
packing materials for the carrier or place of purchase and file a claim for shipping
damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier
within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within
15 days to your service representative.
Safety Precautions
Read the following precautions before you install the UPS.
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you
should follow during installation and maintenance of the UPS and batteries.
Please read all instructions before operating the equipment and save this manual for
future reference.
WARNING
This UPS contains its own energy source (batteries). The output receptacles
may carry live voltage even when the UPS is not connected to an AC supply.
Do not remove or unplug the input cord when the UPS is turned on. This
removes the safety ground from the UPS and the equipment connected to
the UPS.
To reduce the risk of fire or electric shock, install this UPS in a temperature
and humidity controlled, indoor environment, free of conductive
contaminants. Ambient temperature must not exceed 40°C (104°F). Do not
operate near water or excessive humidity (95% max).
To comply with international standards, the sum of earth leakage current
from the load connected to the UPS must not exceed 1.5 mA.
Installing the UPS
The following steps explain how to install the UPS. See “UPS Rear Panels” on page 9 for
the rear panel of each model.
Please see a typical installation (fig 2)
1. If you are installing power management software, connect your computer to the
USB port or UPS communication port using the supplied cable(see page12 and 13).
NOTE
If you need to change the factory–set defaults for the output voltage or input
voltage range, see “Voltage Configuration” on page 11 before installing the UPS.
2. Unplug the power cord from your largest load. Plug this power cord into the male
inlet of your UPS. You do not need to remove the cord from the wall outlet.