Eaton PW9130N6000T-EBM Fiche technique Page 3

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 3
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 2
Rev 1 Page 3 of 3
Eaton 9130 700-6000VA Tower UPS Technical Specification
MATCHING EXTERNAL BATTERY MODULES
UPS Rating
1000VA 1500VA 2000VA & 3000VA
6000VA
EBM Model PW9130N1000T-EBM PW9130N1500T-EBM PW9130N3000T-EBM PW9130N6000T-EBM
EBM Battery Configuration 2 strings of 3 x 12V9Ah 2 strings of 4 x 12V9Ah 2 strings of 8 x 12V9Ah 2 strings of 20 x 12V7Ah
EBM Dimensions (mm):
W x D* x H
160W x 383D x 231H** 160W x 435D x 231H** 214W x 410D x 325H** 242W x 542D x 575H mm
*Allow 100mm rear clearance for connections ** Height includes rubber feet
Weight (kg) 18.5 24.3 50.0 111
BATTERY RUN TIMES NOTE: Battery times are approximate and vary depending on age, temperature and load configuration.
Minutes @ Full / Half Load Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs
700VA/630W 5 / 14 - - - -
1000VA/900W 6 / 19 32 / 68 51 / 111 81 / 193 100 / 246
1500VA/1350W 5.5 / 14 25 / 62 46 / 112 69 / 172 90 / 222
2000VA/1800W 11 / 28 44 / 96 79 / 168 115 / 258 162 / 336
3000VA/2700W 6 / 16 21 / 60 52 / 100 66 / 169 94 / 215
6000VA/5400W 6 / 19 33 / 78 64 / 148 96 / 211 130 / 266
BYPASS CHARACTERISTICS
Type of bypass Automatic Bypass
Transfer Time Online mode: 0ms (no break), High Efficiency Mode: 10ms maximum (due to loss of utility)
Output Overload (Bypass
Mode)
Level 1: 100-110%: Activates Overload alarm
Level 2: >110-130% UPS shuts down after 5 minutes
Level 3: >130-150%: UPS shuts down after 15 seconds (700-3000VA), 30 seconds (6000VA)
Level 4: >150%: UPS shuts down after 300ms
Vue de la page 2
1 2 3

Commentaires sur ces manuels

Pas de commentaire