9140 runtimes (in minutes)
UPS
Internal +1 +2 +3 +4
VA Watts Batteries EBM EBMs EBMs EBMs
1250 1000 80 137 189 275 365
2500 2000 31 61 99 138 181
3750 3000 18 38 68 92 121
5000 4000 12 27 52 69 90
6250 5000 9 21 42 55 72
7500 6000 7 17 35 46 60
8750 7000 6 14 31 40 51
10,000 8000 5 12 27 35 45
9140 products and services
Part Input Output Dimensions Weight
Model number connection connections (H x W x D, inches) (lb)
200–240 Vac in (single-phase)/200–240 Vac out
User selectable 380–415 Vac in (three-phase)/220–240 Vac out (single-phase) for hardwire models
PW91407500HW 103005093-6591 Hardwired Hardwired(3)C19&(2)C13 10.5(6U)x17.2x31.1 254
PW914010000HW 103004728-6591 Hardwired Hardwired(3)C19&(2)C13 10.5(6U)x17.2x31.1 254
PW91407500 103005094-6591 IEC309-60Acord IEC309-60Acord,(4)C19 10.5(6U)x17.2x31.1 265
PW914010000 103004727-6591 IEC309-60Acord IEC309-60Acord,(4)C19 10.5(6U)x17.2x31.1 265
9140 Extended Battery Modules
PW91403UEBM
1
103004729-6591 5.25(3U)x17.2x26.0 175
Step-Down Transformer
Catalog Part Output Dimensions Weight
Number number connections (H x W x D, inches) (lb)
EXRTL9140-XFMR3U 103007853-6591 (2)L6-30R,(8)5-15/20R 5.14x17.5x22.3 190
1. Up to four EBMs can be connected to a single 9140
9140 connectivity options
Part number Description
116750221-001 ConnectUPS-XWeb/SNMPcard
103005425-5591 Modbuscard
1018460 Relaycard(AS/400compatible)
103003055 Industrialrelaycard
116750224-001 EnvironmentalMonitoringProbe(EMP)(requiresConnectUPSWeb/SNMPX-Slotcard)
Input terminal
block
REPO connector
USB port
X-Slot
communication
bay
(4) 20A/250V output
circuit breakers
(3) C19 output
receptacles
EBM
connector
Output
terminal
block cover
Serial port
(2) C13 output
receptacles
Bypass input
9140 hardwire
9140 EBM (rear view)9140 (rear view)
EBM battery connector
Circuit breaker
3
www.eaton.com/powerquality 1.800.356.5794